Short-Circuit Current Calculator

A rough estimate of fault current at a transformer's secondary terminals — not a substitute for a proper fault level study.

Read before using this one: this figure only covers the transformer's own impedance at its secondary terminals. It ignores the upstream source fault level, cable impedance, and everything downstream — all of which reduce the real fault current at your switchboard. Never use this number alone to select or verify a breaker's interrupting (kA) rating. That requires a full fault level study by a licensed designer.

Transformer secondary fault current

Isc = Full-load current ÷ (impedance % ÷ 100)

Check the transformer's nameplate — typically 4–6% for distribution transformers.

Approx. three-phase fault current

0 kA

Transformer-terminal only — the real figure at your switchboard will be lower once source and cable impedance are included. Get a proper fault level study before relying on this for protective device selection.

Export this result as a PDF

A clean, branded PDF of your inputs and result — handy for records or sending on.

Please note: General guidance only — verify against the current standard before relying on this result. Not a substitute for a licensed electrical design.

Get a quote

Need the real numbers signed off?

This tool is a starting point. Get a licensed design or on-site assessment for anything going to certification.

  • Instant online quote for test & tag
  • Booked in as soon as we can fit you in
  • Certificate + asset register within 24h of completion

We'll get back to you promptly. Prefer to talk now? Call 0404 961 061.

Need it done, not just calculated?

Switchboard Upgrades

Replace old ceramic-fuse boards with a modern, compliant switchboard built for your load.

Get a quote
CallGet Quote