RCD Trip-Time Reference Card

Maximum trip times and testing intervals under AS/NZS 3760 — the numbers electricians and site managers check most often, in one place.

RCD typeMust trip within
Type II (30 mA)300 ms
Type I (10 mA)40 ms
RCD typePush-button interval
Portable RCDsEvery 3 months (construction/high-risk: daily or before each use, whichever is longer)
Fixed RCDs (switchboard)Every 6 months
RCD typeTrip-time interval
Portable RCDsEvery 6 months (construction: 3 months; some low-risk 12 months)
Fixed RCDs — commercial / industrialEvery 12 months
Fixed RCDs — residential-type / low-riskUp to 2 years

Please note: These intervals are indicative, based on AS/NZS 3760:2022 (Table 2.4) and related standards. They are minimum recommendations — your actual interval must be set by a documented risk assessment for your specific site and may be shorter. This is general guidance only and is not a compliance determination for your workplace. Contact us for a site-specific assessment.

Not sure which interval applies to your site, or want the equipment testing intervals too? Try theInterval Checker, or read more onRCD & safety-switch testing.

Get a quote

Overdue for a trip-time test?

Tell us how many switches and where — we'll come back with a straight quote, promptly.

  • Instant online quote for test & tag
  • Booked in as soon as we can fit you in
  • Certificate + asset register within 24h of completion

We'll get back to you promptly. Prefer to talk now? Call 0404 961 061.

Need it done, not just calculated?

RCD & Safety-Switch Testing

Push-button and trip-time testing on fixed and portable safety switches, to AS/NZS 3760.

Get a quote
CallGet Quote